CHEWATEC MC-II-ORPs

Measuring and control unit CHEWATEC MC II for measurement and control of ORP (redox) for use in potable water treatment, swimming pools/hot tubs at up to 60°C / 3 bar. The control unit comes with the ORP sensor.


Control

◼ Bidirectional PID control    

Inputs

◼ Sensor input for the relevant measured variable

◼ Temperature sensor input: Pt 1000

◼ 1 digital input as a remote control input for the functions pause control / sample water fault

Outputs

◼ 2 pulse frequency outputs for the control of metering pumps

◼ 1 configurable 0/4...20 mA, max. load 450 Ω

◼ 2 output relays used as limit values / pulse lengths

Voltage supply

◼ 100 - 230 VAC, 50/60 Hz

Permissable operating temperature

◼ -10 ... +50 ° C

Enclosure rating

◼ IP 65

Dimensions

◼ 198 x 200 x 76 mm (H x W x D)

Weight

◼ 0,8 kg

Areas of application

◼ Measurement of the ORP value in potable water treatment, food and beverage industry and swimming pools


Type

Product

Parameter

Application

MC-II-pHs

CHEWATEC MC II

pH

Drinking water, swimming pools

MC-II-pHr

CHEWATEC MC II

pH

Contaminated water

MC-II-ORPs

CHEWATEC MC II

ORP

Drinking water, swimming pools

MC-II-ORPr

CHEWATEC MC II

ORP

Contaminated water

MC-II-CLF

CHEWATEC MC II

Free Chlorine

Drinking water, swimming pools

Write a review

Note: HTML is not translated!
    Bad           Good

CHEWATEC MC-II-ORPs

  • Brand: CheWaTec
  • Product Code: MC-II-ORPs
  • Availability: Pre-Order

Varianty produktu

Názov Cena Košík
CHEWATEC MC-I-pHr
CHEWATEC MC-I-ORPs
CHEWATEC MC-I-ORPr
CHEWATEC MC-I-CLF
CHEWATEC MC-I-CONs
CHEWATEC MDS V - pH - ORP
CHEWATEC MDS V - ORP
CHEWATEC MDS V - CONs
CHEWATEC MDS V - pH - CLF
CHEWATEC MDS VII - pH
CHEWATEC MDS VIII - pH - ORP
CHEWATEC MDS X

Tags: pH, control