Measuring and control unit CHEWATEC MC I for measurement and control of conductivity for use in clear waterwith constant temperature with conductivity 0.01 mS...20 mS, max. temperature 80°C / 16 bar. The control unit comes with the conductivity sensor (CON probe).
Control
◼ Monodirectional PID control with selectable control direction
Inputs
◼ Sensor input for the relevant measured variable
◼ Temperature sensor input: Pt 1000
◼ 1 digital input as a remote control input for the functions pause control / sample water fault
Outputs
◼ 1 pulse frequency output for the control of metering pumps
◼ 1 active 0/4...20 mA output configurable as a measured or control variable, max. load 400 Ω
◼ 1 output relay can be used for a blowoff valve
Voltage supply
◼ 100 - 230 VAC, 50/60 Hz
Permissable operating temperature
◼ -10 ... +80 ° C
Enclosure rating
◼ IP 67
Dimensions
◼ 135 x 125 x 75 mm (H x W x D)
Weight
◼ 0,5 kg
Type |
Product |
Parameter |
Application |
MC-I-pHs |
CHEWATEC MC I |
pH |
Drinking water, swimming pools |
MC-I-pHr |
CHEWATEC MC I |
pH |
Contaminated water |
MC-I-ORPs |
CHEWATEC MC I |
ORP |
Drinking water, swimming pools |
MC-I-ORPr |
CHEWATEC MC I |
ORP |
Contaminated water |
MC-I-CLF |
CHEWATEC MC I |
Free Chlorine |
Drinking water, swimming pools |
MC-I-CONs |
CHEWATEC MC I |
Conductivity |
Clear water |
MC-I-CONr |
CHEWATEC MC I |
Conductivity |
Contaminated water |